DF-A+
DF-A with Arc-Killer and gas exhaust duct
Standard equipment
- Three phase load break switch of the type RV44, class E3 according to IEC 62271-103, interruption in SF6
- Interlocked earthing switch with a making capacity of 63 kA
- Support for cable terminal box
- Door interlock
- Socket for capacitive voltage presence indicator with phase comparison possibility
- Low voltage compartment
- Integrated SV-25 Arc-Killer
- Gas exhaust duct on the rear side of the cubicle
Options
- Set of auxiliary contacts for the load break switch
- Set of auxiliary contacts for the earthing switch
- Key lock on the load break switch
- Key lock on the earthing switch
- Key lock on both
- No door interlock
- Motor operation: 24-48-110 V AC/DC or 220 V AC
- Short circuit indicator (to be specified by the customer at order)
- Voltage presence indicators
- Plinth of a height of 200 mm, 300 mm or 400 mm (other dimensions available on request)
- Floor pans
- Push button control
- Remote control
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 |
---|---|---|---|
Rated current | A | 800-1250 | 800-1250 |
Short time current | kA | 25 | 25 |
Time of the short time current | s | 1 | 1 |
Width | mm | 500 | 500 |
Depth | mm | 1050 | 1050 |
Height | mm | 1700 | 1700 |
Weight | kg | 210 | 210 |