DF-DT(G)
Compact and multi-functional cubicle for the protection of a generator
Standard equipment
- Three phase load break switch of the type RV44, class E3 according to IEC 62271-103, interruption in SF6
- Interlocked earthing switch with a making capacity of 63 kA
- Support for cable terminal
- Door interlock
- Sockets for capacitive voltage presence indicators with possibility of phase comparison
- Low voltage compartment
Advantages
- Sharp price and compact product
- Simple medium voltage configuration (small dimensions and modular type)
- Easy to install around or near the generator and the control board (IAC 16kA/1s – AFLR and no long MV & LV cables)
- Over voltage protection of the generator with lightning arresters
- Easy handling (no complex synoptic scheme)
- Extra advantages in comparison to the competition: excellent safety of the operator through:
- Cubicles with internal arc protection IAC AFL 16kA/1s
- Interlocked and visible earthing switch (no use of unreliable door contacts in the event of unforeseen opening of the panel and no use of grounding ends required to make a visible earthing)
- Three phase load break switch (no use of removable copper strips required for a visible interruption)
- Double position indicator, combination of the load break switch and the circuit breaker
- KEMA tested according to the latest IEC standards for medium votage cubicles
- Maintenance free and reliable
- Flexible options
Options
- Current transformer (to be specified by the customer)
- Voltage transformer (to be specified by the customer)
- Set of auxiliary contacts on the load break switch maximum 3NO/NC
- Set of auxiliary contacts on the earthing switch maximum 2NO/NC
- Key lock on the load break switch
- Key lock on the earthing switch
- Key lock on both
- No door interlock
- Available auxiliary voltages: 24-48-110 V AC/DC or 220 VAC
- Short circuit indicator (to be defined by the customer)
- Earthing balls upstream of the circuit breaker
- Voltage presence indicator
- Plinth with a height of 200 mm, 300 mm or400 mm (other dimensions available on request)
- Floor plates
- Push button control on the load break switch
- Remote control for the load break switch
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 | 24 |
Rated current | A | 800-1250 | 800-1250 | 630-1250 |
Short time current | kA | 16/20/25 | 16/20/25 | 16/20 |
Time of the short time current | s | 1/2/3 | 1/2/3 | 1/2/3 |
Width | mm | 750 | 750 | 750 |
Depth | mm | 940 | 940 | 940 |
Height | mm | 1700 | 1700 | 1700 |
Height between the bottom and the cable terminal box | mm | 445 | 450 | 450 |
Weight | kg | 360 | 360 | 360 |
Options for the circuit breaker
- Direct / time delayed under voltage release
- Additional auxiliary contacts
- Operation counter
- Automatic reclosing
- Remote control
- Interlock
Requested specifications for the choice of the circuit breaker: Short time current, rated current, rated voltage, power to be protected.