DF-C-750
Metering cubicle
Standard equipment
- 3 CT’s xA => 5A
- 3 VT’s xV => 110V, V3
Options
- Additional current transformers
- Additional voltage transformers with or without MV and LV protection
- Support for the installation of the metering transformers
- Metering system with 3 CT’s and 3 VT’s
- Metering system with kWh meter and kVARh meter (specifications to be supplied by the customer)
- Metering system: current metering
- Metering system: voltage metering
- Plinth with a height of 200 mm, 300 mm or 400 mm (other dimensions available on request)
- Floor panels
- Low voltage compartment
- Protection cabinet for the protection of the voltage circuits
Following specifications for the CT’s have to be specified by the customer: Primary current, secondary current, power and accuracy class, insulation class, thermical withstand current
Following specifications for the VT’s have to be specified by the customer: Primary voltage, secondary voltage, power and accuracy class, insulation class
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 | 24 |
---|---|---|---|---|
Rated current | A | up to 1250 | up to 1250 | up to 630 |
Short time current | kA | 25 | 25 | 20 |
Time of the short time current | s | 1 | 1 | 1 |
Width | mm | 750 | 750 | 750 |
Depth | mm | 1050 | 1050 | 1050 |
Height | mm | 1700 | 1700 | 1700 |
Weight | kg | 55 | 55 | 55 |
Possible executions
- Input under left, output under right
- Input under right, output under left
- Input under left, output top right
- Input under right, output top left