DF-P
Protection or transformer cubicle with load break switch / fuse combination
Standard equipment
- Three phase load break switch RV44, class E3 according to IEC 62271-105, interruption in SF6
- Double earthing switch with mutual interlock
- Base for HRC fuses
- e = 292 mm DIN 10 at 17.5 kV
- e = 442 mm DIN 20 at 24 kV
- UTE
- Three phase fuse trip in case of the melting of one of the fuses
- Switch-off mechanism through hitting bolt
- Door interlock
- Sockets for capacitive voltage presence indicators
- Low voltage compartment
Options
- Set of auxiliary contacts on the load break switch
- Set of auxiliary contacts on the earthing switch
- Key lock on the load break switch
- Key lock on the earthing switch
- Key lock on both
- Tripping coil*
- Direct / time delayed under voltage release*
- Closing coil*
- Motor operation*
- HRC fuses and/or spare fuses
- Default contact “fuse melted”
- Automatic recloser
- Set of 2 or 3 voltage transformers
- Voltage presence indicators
- Plinth of a height of 200 mm, 300 mm or 400 mm (other dimensions available on request)
- Floor panels
- Push button control
- Remote control
* available voltages: 24 V AC/DC, 48 V AC/DC, 110 V AC/DC, 220 V AC
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 | 24 |
---|---|---|---|---|
Rated current | A | 800-1250 | 800-1250 | 630 |
Short time current | kA | 25 | 25 | 20 |
Time of the short time current | s | 1 | 1 | 1 |
Width | mm | 500 | 500 | 500 |
Depth | mm | 1050 | 1050 | 1050 |
Height | mm | 1700 | 1700 | 1700 |
Height between bottom and cable terminal | mm | 460 | 460 | 415 |
Size of the fuses | mm | 292 (DIN) | 292 (DIN) | 442 (DIN)/UTE |
Weight | kg | 210 | 210 | 210 |