DF-A
Incoming or cable cubicle with RV44 load break switch and interlocked earting switch
Standard equipment
- Three phase load break switch of the type RV44, class E3 according to IEC 62271-103, interruption in SF6
- Interlocked earthing switch with a making capacity of 63 kA
- Support for cable terminal
- Door interlock
- Capacitive voltage presence indicator holder with possibility of phase comparison
- Low voltage compartment
Options
- Set of auxiliary contacts on the load break switch
- Set of auxiliary contacts on the earthing switch
- Key lock on the load break switch
- Key lock on the earthing switch
- Key lock on both
- Motor operation: 24-48-110 V – AC/DC or 220 V AC
- Short circuit indicator (to be specified by the customer at order)
- Voltage presence indicators
- Plinth of a height of 200 mm, 300 mm or 400 mm (other dimensions on request)
- Floor panels
- Push button control
- Remote control
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 | 24 |
---|---|---|---|---|
Rated current | A | 800-1250 | 800-1250 | 630 |
Rated short circuit current | kA | 25 | 25 | 20 |
Time of the rated short circuit current | s | 1 | 1 | 1 |
Width | mm | 500 | 500 | 500 |
Depth | mm | 1050 | 1050 | 1050 |
Height | mm | 1700 | 1700 | 1700 |
Height between bottom and cable terminal | mm | 945 | 945 | 835 |
Height between bottom and cable terminal support | mm | 445 | 445 | 445 |
Weight | kg | 180 | 180 | 180 |