DR-6C-3KT (compact version)
Standard equipment
- Triple-phase load break switch RV 50, class E3 according to IEC 62271-103, SF6-insulation
- Interlocked earthing switch with making capacity up to 50 kA
- Cable support
- Door interlock
- Sockets for capacitive voltage detector with parallel testing possibility
- Low-voltage compartment
- Gland plates
Options
- Set of auxiliary contacts on load break switch
- Set of auxiliary contacts on earthing switch
- Key interlock on load break switch
- Key interlock on earthingswitch
- Key interlock on both
- No door interlock
- Motor operation: 24-48-110 V – AC/DC of 220 V AC
- Short-circuit indicator (to be specified by the customer when the order is placed)
- Voltage indicators
- Cubicle base: 200 mm, 300 mm or 400 mm height (Other dimensions on request)
- Button press control
- Remote control
- Arc-killer SV-50
- Side or top extension
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 | 24 |
---|---|---|---|---|
Rated current | A | 630 | 630 | 630 |
Rated short circuit current | kA | 20 | 20 | 20 |
Time of the rated short circuit current On request |
s | 1 – 3 | 1 – 3 | 1 – 3 |
Width | mm | 1271 | 1271 | 1271 |
Depth | mm | 860 | 860 | 860 |
Height | mm | 1422 | 1422 | 1422 |
Height between ground and end socket | mm | 745/325 | 745/325 | 745/325 |
Fuse size | mm | 292 (DIN) | 292 (DIN) | 292/442 (DIN)/UTE |
Weight | kg | 600 | 600 | 600 |