DF-LK
Busbar coupling cubicle
Standard equipment
- Two three phase load break switches of the type RV 44, class E3 according to IEC 62271-102, interruption in SF6
- Door interlocking
- Low voltage compartment
Options
- Sockets for capacitive voltage presence indicators on load break switch(es) 1 and/or 2
- Set of auxiliary contacts on load break switch(es) 1 and/or 2
- Key lock on load break switch(es) 1 and/or 2
- Key lock on earthing switch
- Mechanical interlock between the load break switches
- No door interlock
- Motor operation on load break switch(es) 1 and/or 2: 24-48-110 V DC or 110-220 V AC
- Earthing switch
- Earthing balls on load break switch(es) 1 and/or 2
- Earthing balls outside the cubicles
- Capacitive voltage indicators on load break switch(es) 1 and/or 2
- Plinth of a height of 200 mm, 300 mm or 400 mm (other dimensions possible available on request)
- Floor panels
- Push button control on load break switch(es) 1 and/or 2
- Remote control of the load break switch(es) 1 and/or 2
- Current transformers
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 | 24 |
---|---|---|---|---|
Rated current | A | 800-1250 | 800-1250 | 630 |
Short time current | kA | 25 | 25 | 20 |
Time of the short time current | s | 1 | 1 | 1 |
Width | mm | 750 | 750 | 750 |
Depth | mm | 1050 | 1050 | 1050 |
Height | mm | 1700 | 1700 | 1700 |
Weight | kg | 245 | 245 | 245 |