DF-K
Cable or bus riser cubicle
Options
- Sockets for capacitive voltage presence indicators
- Capacitive voltage indicators
- Short circuit detectors (to be specified by the customer at order)
- Earthing switch
- Set of auxiliary contacts on the earthing switch
- Key lock on the earthing switch
- Earthing balls
- Current transformers in the busbar
- Voltage transformers in the busbar with or without protection
- Plinth of a height of 200 mm, 300 mm or 400 mm (other dimensions available on request)
- Floor panels
- Door interlock
Specifications and dimensions
Rated voltage | kV | 12 | 17,5 | 24 |
---|---|---|---|---|
Rated current | A | up to 1200 | up to 1200 | up to 630 |
Short time current | kA | up to 25 | up to 25 | up to 20 |
Time of the short time current | s | 1 | 1 | 1 |
Width | mm | M | M | M |
Depth | mm | 1050 | 1050 | 1050 |
Height | mm | M | M | M |
Weight(*) | kg | 55 | 55 | 55 |
* without ewuipment / M stays for custom made